Presentation No 812 – A proposed methodology to reduce heat pump size with integrated thermal energy storage – 14th IEA Heat Pump Conference, Chicago, USA

Thermal energy storage (TES) offers a unique storage solution wherein heat is stored for later use to thermally condition an application. Heat pumps (HPs) move heat from relatively cold to a relatively hot with an input of work. Integrating TES into a HP system adds a third temperature body, and the HP can be selectively coupled to operate between any two bodies: a constant temperature application, a temporally fluctuating ambient temperature, or a constant temperature TES. Since the HP-TES system enables operation under different conditions depending on the pair of temperature bodies, changes in efficiency and capacity can be expected. Thus, TES can shift HP operation to more favorable conditions to deliver heat to the application. Consequently, TES increases the apparent capacity of the HP which might enable a nominally smaller HP to be used effectively for an application. This paper outlines a method by which TES can reduce the size of a HP without sacrificing heat delivered to the application. The method is demonstrated for a building cooling application which realized a reduction in nominal HP size from 3 tons to 2.4 tons.

Download

Publication type Conf Proceedings Paper

Publication date 15 May 2023

Authors Jason Hirschey, Kyle R. Gluesenkamp, Bo Shen, Zhenning Li, Samuel Graham

Keywords thermal energy storage; heat pump

Order nr Presentation No 812

Download