Paper No 128 – Study on layer short mechanism and discharge pattern in refrigerant compressor for refrigerants with disproportionation reaction like HFO-1123 – 13th IEA Heat Pump Conference, Jeju, Korea
HFO-1123, one of the low GWP refrigerants, will be decomposed with receiving large amounts of energy under high temperature and pressure condition. Short-circuit between motor winding wires caused by an insulation breakdown, i.e. layer short, in refrigerant compressors could be a trigger of the disproportionation reaction of HFO-1123. In this study, the layer short mechanism and the electric energy discharged by the layer short of winding wire in the refrigerant compressor were investigated. A compressor equipped with a short-circuit generation mechanism in a compressor shell was used to measure the electric energy by the layer short during the compressor operation. Experiments were carried out mainly with the short-circuit between both ends of a mainwinding as the worst case. There were several short-circuit patterns and the maximum current was observed to be 700 - 900 A and the electric energy was about 160 J. When the short-circuit occurred between terminals of the main-winding and an auxiliary-winding, the motor stopped while the electricity was continuously supplied, and temperature of the winding wire increased approximately 2.5?/s.