FURTHER CO2 EMISSION MITIGATION BY MAKING OF SUPPLY WARM WATER TEMPERATURE LOWER IN THE HEAT PUMP & EVAPORATIVE HUMIDIFIER SYSTEM
It is known that the heat pump & evaporative humidifier can mitigate CO2 emission at heating and humidifying of air conditioning system, instead of steam heater and steam humidifier. And for the further CO2 emission mitigation, it is known that to attempt making of the supply warm water temperature a low temperature than 45°C (113°F) so far, because it can increase the COP of the heat pump. But doing so, the power consumption of fan at the makeup air handling unit will increase, because of the number of rows of hot-water coils that exchange the heat of the warm water to air increases. So it is general to select the supply warm temperature 45°C (113°F) so far. In this paper it will be reported that the temperature of supply warm water of 30-35°C (86-95°F) is better for CO2 emission mitigation at the total air conditioning system. And to select appropriate warm water temperature is a point of the COP improvement. As a result, the CO2 emission mitigation with the heat pump is more possible.