DEVELOPMENT OF ABSORPTION HEAT PUMP CHILLERS WITH IMPROVED HEATING EFFICIENCY BY APPLYING HEAT PUMP CYCLE

Improvements have continually been made in the performance of absorption chiller-heaters in the cooling mode. On the other hand, the heating performance has not been improved because of the difficulty in constructing an appropriate heat pump cycle. The purpose of this study is to improve the heating performance of absorption chiller-heaters by using a heat pump cycle in the heating mode. We call these machines “Absorption heat pump chillers (AHPC)”. The main difficulty of constructing an AHPC is reducing the pressure of the high temperature generator. We applied two-stage evaporator and absorber to reduce the pressure. Consequently, we developed two types of AHPCs. The first type is a doubleeffect absorption heat pump chiller. In the heating mode, this machine uses 12°C water as a heat source to provide 45°C water for space heating. The coefficient of performance (COP) in the heating mode was calculated at 2.2. The second type is a double-output absorption heat pump chiller. This provides chilled and hot water simultaneously. The experimental results from this machine showed a combined heating and cooling COP of 3.3.

Download

Publication type Conf Proceedings Paper

Publication date 16 September 2011

Authors T. Fujii, S. Uchida, N. Nishiyama

Keywords absorption heat pump, heating efficiency, heat recovery

Order nr HPP-CONF10

Download