Paper No 248 – Analysis of the mixture refrigerant R600/R245fa using in high temperature heat pump – 13th IEA Heat Pump Conference, Jeju, Korea

High temperature heat pump (HTHP) is an effective equipment to recovery industrial waste heat and it has a wide application potential. The choice of refrigerant has important influence on the efficiency of HTHP. In this paper, the performance parameters of the mixture refrigerant R600/R245fa using in HTHP were tested. Compared with the R245fa, the mixture refrigerant R600/R245fa has higher heating capacity and lower COP. But the COP of the HTHP system also can maintain above 3.0 when the temperature of condenser outlet water is at 100 ? and 35 ? temperature lift. Analysis shows that R600/R245fa is suitable for HTHPs with higher condenser outlet water temperature and heating capacity demand. And its low GWP also has good environmental benefits.

Download

Publication type Conf Proceedings Paper

Publication date 31 August 2021

Authors Xiaohui Yu, Chang Xu

Keywords mixture refrigerant; High temperature heat pump; cycle performance

Order nr Paper No 248