Paper No 128 – Study on layer short mechanism and discharge pattern in refrigerant compressor for refrigerants with disproportionation reaction like HFO-1123 – 13th IEA Heat Pump Conference, Jeju, Korea

HFO-1123, one of the low GWP refrigerants, will be decomposed with receiving large amounts of energy under high temperature and pressure condition. Short-circuit between motor winding wires caused by an insulation breakdown, i.e. layer short, in refrigerant compressors could be a trigger of the disproportionation reaction of HFO-1123. In this study, the layer short mechanism and the electric energy discharged by the layer short of winding wire in the refrigerant compressor were investigated. A compressor equipped with a short-circuit generation mechanism in a compressor shell was used to measure the electric energy by the layer short during the compressor operation. Experiments were carried out mainly with the short-circuit between both ends of a mainwinding as the worst case. There were several short-circuit patterns and the maximum current was observed to be 700 - 900 A and the electric energy was about 160 J. When the short-circuit occurred between terminals of the main-winding and an auxiliary-winding, the motor stopped while the electricity was continuously supplied, and temperature of the winding wire increased approximately 2.5?/s.

Download

Publication type Conf Proceedings Paper

Publication date 31 August 2021

Authors Mitsuhiro Fukuta, Hideyuki Fujimoto, Masaaki Motozawa

Keywords HFO1123, Disproportionation reaction, Compressor, Motor, Layer short, Electric energy

Order nr Paper No 128

Download