O.4.2.3 Experimental Comparison of Different Two-Phase Refrigerant Distribution Devices

For larger air-source heat pumps, especially when trying to minimize the inner volume and the refrigerant content in the evaporator, refrigerant distribution to a high amount of parallel passes through the evaporator is a challenge. As the refrigerant leaves the expansion valve partly evaporated, this 2-phase refrigerant has to be distributed to the passes of the evaporator in a way that ideally all passes get the same amount of liquid. In the frame of the EU-founded project “GreenHeatPump” a novel distributor concept was developed and included in a prototype Heat Pump. This novel distributor and several conventional distributors have been subject to extensive tests on a dedicated test rig. In this paper the test rig is explained in detail and the results for the different distributors are presented.

Download

Publication type Conf Proceedings Paper

Publication date 18 May 2017

Authors Simon Braungardt, Boje Lange, Thore Oltersdorf

Keywords evaporator; two-phase refrigerant; distribution; experimental results; R290

Order nr -