P.3.3.1 Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

A tested loop for high temperature heat pump (HTHP) system with a constant speed scroll compressor using HFC245fa as its refrigerant was designed and built. Theoretical analysis and experiment were carried out under the working condition of condensation temperature from 70? to 120?, temperature rise from 30? to 50?. The theoretical and experimental results both show that heating capacity and coefficient of performance (COP) of the HTHP increase with condensation temperature increasing at fixed temperature rise, and the discharge superheating reduces with condensation temperature increasing at fixed suction superheating and temperature rise. The experimental results show that the outlet temperature of the pressurized water can be heated up to 114?, COP can be as high as 5.18, when condensation temperature and temperature rise are 120? and 49?, respectively.

Download

Publication type Conf Proceedings Paper

Publication date 18 May 2017

Authors Mingyue Huang, Xiangfei Liang, Rong Zhuang

Keywords high temperature heat pump; HFC245fa; scroll compressor

Order nr -

Download