An Experimental Study on the Heat and Mass Transfer of Adsorption Chiller

Adsorption chillers have been receiving considerable attentions as they are energy saving and environmentally benign systems. In this paper, heat and mass transfer experiments of adsorption bed were performed in the batch type adsorption apparatus. The adsorbent and the refrigerant used for the experiment is silica gel and water. Three types of adsorption bed heat exchangers ; fin-tube, heat pipe with both sides and heat pipe with one side, are proposed and experimented. The performance of adsorption bed was analysed by heat transfer rate and adsorption rate with inlet temperature of cooling water. The experimental results show that the adsorption bed of fin-tube type gave best heat transfer rate of 960 W. Also, it is found that the heat pipe with one side showed better performance in the heat transfer rate(540 W) than that of the heat pipe with both sides(340 W) by up to 60%.

Download

Publication type Conf Proceedings Paper

Publication date 24 June 2014

Authors K. J. Bae, D. A. Cha, O. K. Kwon, C. W. Park

Keywords adsorption chiller, adsorption rate, heat and mass transfer, silica gel-water