OPTIMIZATION ANALYSIS FOR LOUVER-FINNES HEAT EXCHANGERS
A series of 3-D computational fluid dynamics analyses along with the simplified conjugate-gradient method were carried out to study the thermal-hydraulic characteristics for the louver-finned heat exchanger. The effects of different louver angles (? = 20o to 28o), and louver pitches (Lp = 0.8 to 1.2 mm) on the heat transfer phenomenon and pressure drop (in terms of Colburn j factor and friction f factor) were investigated in detail. The optimization of the louver angle and louver pitch is carried out by using the simplified conjugate-gradient method. The area reduction ratio using a louver fin relative to the plain surface is the objective function to be maximized. The numerical results showed that both the f and j factors are increased with the increase of the louver angle; while, for a given louver angle, as the louver pitch (Lp) is creased, both the f and j factors are increased. It is also found that, under the optimum conditions, the area reduction ratio could reach up to 28 % to 37% with Reynolds number (based on the fin pitch ) ReFp ranging from 400 to 1600.