FIELD MEASUREMENT ON THE PERFORMANCE OF VRV SYSTEM BY PROBE INSERTION METHOD

This paper reports on the Probe Insertion Method for On-site Evaluation of the Variable Refrigerant Flow (VRF) system and the evaluation results for both Gas Engine- Driven (GHP) and Electrical Motor-Driven (EHP) VRF systems. The probe insertion method consists of both computer modelling and direct measurements of the heat exchange of the outdoor unit. The actual measurements were conducted in the prefectures of Tokyo, Osaka, Kochi and Hokkaido, Japan. These candidate buildings consisted of an office, a government office and a school cafeteria. The experiment was carried out from summer to winter to see both the effects of cooling and heating. In this study, the authors detail the probe insertion method, which is a simple measurement technique, and also present the results from the actual measurements.