FIELD TEST STUDY ON THE PERFORMANCE OF AIR SOURCE HEAT PUMP IN LOW TEMPERATURE IN BEIJING

Under the abnormal weather, such as -16.5°C~-6°C of low temperature and snow, air source heat pump (ASHP) unit was tested continuously for 80 hours in Beijing. The unit’s operation characteristics in low temperature were analyzed in the aspects of operation performance, heating performance and heating effects. The results shown that in the average outdoor temperature of -11°C, average COP reached 2.21 and heating demands were satisfied. It was pointed out that the mal-defrost operations together with the frequent start-stop operations were the key problems to influence the stability of system’s heating performance.

Download

Publication type Conf Proceedings Paper

Publication date 23 September 2011

Authors W. Wang, J. Xiao, Q. Guo, W. Lu, Y. Zhao

Keywords ASHP, low temperature, field test, heating performance