HIGH EFFICIENT HEAT PUMPS FOR SMALL TEMPERATURE LIFT APPLICATIONS

Today, one of the most promising type of heating system for achieving significant primary energy savings in heating of buildings is a heat pump. Their efficiency as measured by the coefficient of performance (COP) is closely related to the inner temperature lift, i. e. the temperature difference between condensation and evaporation. The potential for highly efficient systems is not fully exploited as standard heat pumps are designed for large lifts of 30–60 K. The integration of small temperature lift heat pumps in efficient overall heating systems leads to a considerable reduction in the use of primary energy and operating costs. The development of efficient heat pumps for small temperature lifts requires a new approach in the design and selection of the components. In order to demonstrate the improved efficiency, a system for small internal temperature lifts was developed and tested. By using geothermal heat probes and efficient heat delivery and supply systems a COP above 9 can be achieved for a temperature lift of 20 K. The heat pump can also be employed as a highly efficient chiller for building cooling. For an evaporation temperature of 15°C, the cooling COP is 11.5 at a temperature lift of 12.5 K.

Download

Publication type Conf Proceedings Paper

Publication date 23 September 2011

Authors I. Wyssen, L. Gasser, M. Kleingries, B. Wellig

Keywords heat pumps for small temperature lift, guidelines for the planning and design, experimental investigations, improvement in efficiency

Order nr HPP-CONF10

Download