DEVELOPMENT AND EXPERIMENTAL INVESTIGATION OF A NOVEL10 KW AMMONIA/WATER ABSORPTION CHILLER – CHILLII® PSC – FOR AIR-CONDITIONING AND REFRIGERATION SYSTEMS

The content of the paper is the development, experimental investigation and simulation of the thermally driven single-effect ammonia/water absorption heat pump/chiller for air-conditioning and refrigeration systems for residential, commercial and industrial applications. The novel chillii® PSC has a cooling capacity of 10 kW and compact design. The peculiarities of the chiller are the special design of the membrane pump for the solution circulation, the mechanical solution controller and the vertical falling-film tubular absorber and evaporator, respectively. The experimental investigations at the two test stands of SolarNext and Pink showed that the chiller reaches evaporator outlet temperatures from 15°C down to -5°C at heating temperatures from 65°C to 115°C. The investigated recooling temperatures are between 24°C and 40°C. A TRNSYS simulation of a solar air-conditioning system with a model of the chillii® PSC10 was carried out to analyse the performance behaviour of such system. For Zurich and Madrid the results showed that the system design is sufficient for different climatic conditions and collector as well as heat storage sizes.

Download

Publication type Conf Proceedings Paper

Publication date 22 May 2008

Authors U. Jakob, K. Spiegel, W. Pink

Keywords heat pump, chiller, absorption, ammonia/water, simulation

Order nr HPP-CONF9

Download