A NEW TEST AND EVALUATION METHOD OF ANNUAL ENERGY EFFICIENCY OF MULTIPLE AIR-CONDITIONERS FOR BUILDINGS

We made the partial load performance tests of multiple air-conditioners for buildings powered by electric motors, the rating cooling performance of which was 56 kW, by using the air-enthalpy method testing apparatus. The coefficient of performance (COP) and annual energy consumption measured by those tests were closely compared with those predicted by the current calculating method provided by Japanese Industrial Standards (JIS B 8616:2006). The performance of the air-conditioner changed depending on the outdoor air temperature and the indoor thermal load. The current calculating method could not reproduce the deteriorations of COPs that appeared under the low thermal load operating conditions in both the cooling and heating seasons. As a result it seriously underestimated the annual energy (electricity) consumption; the error amounted to about 20 % of the measured value of the annual electric energy consumption. Based on these results, we proposed new testing conditions for the performance evaluation and a calculation method of the annual electricity consumption that could improve noticeably the accuracy of the estimation of the annual electricity consumption.

Download

Publication type Conf Proceedings Paper

Publication date 22 May 2008

Authors C. Watanabe, K. Nagamatsu, H. Nakayama, M. Hirota, E. Ohashi

Keywords heat pump, coefficient of performance, partial load performance, office building, annual energy consumption

Order nr HPP-CONF9