PREDICTION OF ICE AND FROST FORMATION IN THE FIN TUBE EVAPORATORS FOR AIR/WATER HEAT PUMPS
In the next few years, the seasonal performance factor of air/water heat pumps will be greatly increased. Success in doing this will depend on two factors: The adaptation of the operating characteristic of the heat pump by the use of continuous power control and the reduction of ice and frost formation. Frost leads to a considerable reduction of the airflow through the evaporator and, therefore, of heat and mass transfer. The formation of ice and frost is influenced by a complex interaction between evaporator, fan characteristic and the characteristic of the heat pump itself. In order to further improve the efficiency of the overall system, a precise prediction of the operation behaviour is required. Based on the theory of simultaneous heat and mass transfer, a mathematical-physical simulation program was developed in the course of the LOREF project. This program allows forecasts of the non-stationary the operation behaviour of the air/water heat pump during ice and frost formation in the evaporator to be made. Here, the greatest challenge was to develop a physical correlation for the properties of the ice and frost deposits during this non-stationary process. Numerous experiments allowed four fields to be distinguished with different characteristics - dependent on the temperature on the boundary layer between air and ice or frost. Comparison with the results of measurements made show that the simulation program developed represents the processes involved in an air/water heat pump during its operation with a high degree of accuracy.